CAD standards

CAD Standards are a set of guidelines for the way Computer-aided drafting (CAD), or (CADD) Computer Aided Design and Drawing, drawings should appear, to improve productivity and interchange of CAD documents between different offices and CAD programs, especially in architecture and engineering.

AEC (Architecture Engineering and Construction) standards

CAD layer standards

Most common:

Samples of standardised layers:

A-B374--E- (ISO13567: agent Architect, element Roof window in SfB, presentation graphic element);
A-37420-T2N01B113B23pro (ISO13567: agent Architect, element Roof Window in SfB, presentation Text#2, New part, floor 01, block B1, phase 1, projection 3D, scale 1:5(B), work package 23 and user definition "pro");
A-G25---D-R (ISO13567: agent Architect, element wall in Uniclass, presentation dimensions, status Existing to be removed);
A-G251-G-WallExtl-Fwd (AEC(UK): agent Architect, element External Wall in Uniclass, presentation graphic element, user definition "WallExtl" and view Forward);
A210_M_ExtWall (BS1192: agent Architect, element External Wall in SfB, presentation model, user definition "ExtWall");
A-E04---E- (ISO13567 SIA 2014: agent Architect, element Stair in SIA classification, presentation graphic element);
A-WALL-FULL (AIA: agent Architect, element Wall, Full height).

Line-thickness

Thickness for pens and plot: 0,13 mm Gray, 0,18 mm Red, 0,25 mm White, 0,35 mm Yellow, 0,50 mm Magenta, 0,70 mm Blue, 1,00 mm Green. In AutoCAD usually parts to be printed in black are drawn in 1 to 7 basic colors. Color layer: Green-Center, Magenta-Measure of length and Blue-Hidden.

Description Line thickness in mm Color Codes
Out Line 0.20 or 0.25 White, Cyan, Yellow,Blue
Hidden Line 0.00 or 0.05 Blue, Gray, 241
Center Line 0.10 or 0.15 Green, Red
Note 0.18 or 0.20 Cyan, Green, 41
Thin Line 0.00 or 0.05 Gray, 08, 111
Reference Line 0.000 Magenta, Gray
Hatch Line 0.000 Magenta, Green, Gray,red
Color-9 to 256 0.000
Dimension line
Leader Line with Arrows 0.000 Gray Color-9,or 8, Red
Text 0.18 or 0.20 Cyan, Green,

Text and dimension

Heights: 2,5 mm, 3,5 mm, 5,0 mm, 7,0 mm (stroke thickness (lineweight) should be 0.1 of the character height). Font styles: "Romans.shx - Romantic Simplex", "ISOCPEUR.ttf". Exceptional use of screen fonts (arial, Times New Roman etc.).

Scales

1:1, 1:10, 1:100 ....
1:2, 1:20, 1:200 ....
1:5, 1:150,1:500 ....
1/8=1'-0"; 3/16"=1'-0", 1/4"=1'-0", 3/8"=1'-0", 1/2"=1'-0", 3/4"=1'-0", 1"=1'-0"

File naming standards

Discipline (1 char), Element (2 char, using SfB Table 1 or Uniclass), Drawing type (1 char, P=preliminary, X=special/xref, L=layout, C=component, S=schedules, A=assembly drawings, K=co-ordination drawing), Unique number (3 char), Revision (1 char, A=emission, B,C,D...= revisions). Samples: A22P012G.dwg (architect, internal walls in SfB, preliminary design, sheet 012, revision G).

Samples: ZE1G-124.dwg, XE1G-100.dwg

Project (unlimited char), Discipline (2 char max, recommended mandatory), Zone (optional), View (1 char, rec.mand.), Level (2 char, rec.mand.), Content (rec.mand.), Sequential number (up to 3 char); Samples: 1234-A-Off-P-M1-Furn-11c.dwg (project #1234, architect, office zone, plan, mezzanine 1, furnitures, version 1.1 revision c), A-P-01-Part (architect, plan, 1st floor, partitions), 1234-A-S-055.dgn (project #1234, architect, section, sheet 055), A-S-xx-AA.dwg (architect, section, full building, section AA), A-P-x-Grid.dgn (architect, plan, all floor, grid), 1838-S-C-P-03 (project 1838, structures, building C, plan, 3rd floor).

Job number (4 char), Agent (1 char), Section (4 char), phase (1 char), sheet number (2 char), revision (2 char) Samples: 0512-A-00A_-1-01-02.dwg Job number (3 char), View (2 char), section (2char), phase (1 char), revision (1 char) Samples: 123p0s2d0.dwg (job 1239, plan, 2nd floor, definitive drawing, emission), 459s0BBD0.dgn (job 123, section B, definitive drawing, emission).

Mechanical CAD standards

Model-based definition

Model-based definition (MBD) is a method of product specification using elements within 3D models as defined by ASME Y14.41-2012. ASME Y14.41-2012 is based upon ASME Y14.5-2009 symbols and definition methods, such as Geometry Dimensioning and Tolerancing (GD&T).

Subscribers of International Organization for Standardization (ISO) have the standards ISO 1101 and ISO 16792 for model-based definition.

Geometry quality

VDA 4955

Product Data Quality

PDQ is a field of PLM relating to the quality of product data, particularly the geometrical and organizational quality of CAD data. Checkers, software that analyze CAD data formats, are often employed before and after data translation. The checkers can check the organization and quality of the data against internal company standards and international or industry standards. These checkers can be built into specific CAD packages or work on a number of CAD file formats.

In 2006/2007 Part 59 of STEP ISO 10303-59 Product data representation and exchange: Integrated generic resource: Quality of product shape data is under development. It defines how to represent quality criteria together with measurement requirements and representation of inspection results.

See also

References

External links

This article is issued from Wikipedia - version of the 10/26/2016. The text is available under the Creative Commons Attribution/Share Alike but additional terms may apply for the media files.